ORDINANCE NO. 226
AN ORDINANCE OF THE CITY COUNCIL OF THE CITY OF
ATASCADERO AMENDING TITLE 8 OF THE ATASCADERO MUNICIPAL
CODE BY THE ADDITION OF CHAPTER 12 RELATIVE TO
EARTHQUAKE HAZARD REDUCTION IN EXISTING
UNREINFORCED MASONRY BUILDINGS
WHEREAS, the State of California has mandated that local
governments shall establish an appropriate and suitable means of
reducing the current level of hazard found in existing
unreinforced masonry buildings; and,
WHEREAS the City of Atascadero, in accordance with state
law, has surveyed and identified probable unreinforced masonry
buildings; and,
WHEREAS, regulations relative to earthquake hazard
reduction are categorically exempt from the California
Environmental Quality Act.
NOW THEREFORE, the City Council of the City of Atascadero,
California, does ordain as follows:
Section 1. Municipal Code Text Change:
A new Chapter 12 is added to Title 8, "Building
Regulations", as contained in the attached Exhibit "A", which is
hereby made a part of this ordinance by reference.
Section 2. Publication.
The City Clerk shall cause this ordinance to be published
once within fifteen ( 15) days after its passage in the
Atascadero News, a newspaper of general circulation, printed,
published, and circulated in the City in accordance with Section
36933 of the Government Code; shall certify the adopting and
posting of this ordinance and shall cause this ordinance and
this certification together with proof of posting to be entered
into the Book of Ordinances of this City.
Section 3. Effective Date.
This ordinance shall go into effect and be in full force
and effect at 12: 01 a.m. on the 31st day after its passage.
Ordinance No. 226
Page 2
On motion by Councilman Lilley and seconded by Councilwoman
Borgeson, the foregoing ordinance was adopted in its entirety by the
following roll call vote:
AYES: Councilmembers Nimmo, Dexter, Borgeson, Lilley and Mayor
Lilley
NOES: None
ABSENT: None
ADOPTED: August 27, 1991 CITY OF ATASCADERO
ALDEN SHIERS, MAYOR
ATTEST:
-vp�&,Aj
LEE RABOIN, City Clerk
APPROVED AS TO FORM:
ART R 14ONTANJON, C ty ttorney
PREPARED BY:
HENRY ENGE ,
Community evelopme t Director
Ordinance No. 226
Exhibit A„
Page No. 1
[[Addition to Title 8 Table of Contents:]]
CHAPTER 12. UNREIN"RCED 11A$ONRY BUILDIRGS
8-12.01--Adoption of the Unreinforced masonry Buildings Ordinance.
8-12.101. Purpose.
8-12.102. Scope
8-12.103. Definitions
8-12.104. Rating Classifications
8-12.105. general Requirements
8-12.106. Administration
8-12.107. Analysis and Design
8-12.108. Materials of Construction
8-12.109. Information Required on Plans.
Ordinance No. 226
Exhibit "A"
Page No. 2
TITLE 8 - BUILDING REGULATI0NS
Chapter 12. Unreinforced Masonry Buildings
8-12.101. Purpose The purpose of this chapter is to promote public safety and
welfare by reducing the risk of death or injury that may result from the effects of
earthquakes on unreinforced masonry bearing wall buildings. Such buildings have
been widely recognized as posing a threat to life because of a history of poor
performance, i.e., partial or complete collapse, during moderate to strong
earthquakes.
The provisions of this chapter are intended as minimum standards for structural
seismic resistance established primarily to reduce the risk of life loss or injury.
Compliance with these standards will not necessarily prevent loss of life or injury
or prevent earthquake damage to rehabilitated buildings. This chapter does not
require alteration of existing electrical, plumbing, mechanical or fire safety
systems (unless they constitute a hazard to life or property), nor require disabled
access or energy conservation alterations.
This chapter provides systematic procedures and standards for identification and
classification of unreinforced masonry bearing wall buildings based on their present
use. Priorities, time periods and standards are also established under which these
buildings are required to be structurally analyzed and anchored. where the analysis
finds deficiencies, this chapter requires the buildings to be strengthened or
demolished.
Qualified Historical Buildings shall comply with the State Historical Building Code
(SHBC) established under Part 8, Title 24 of the California Administrative Code.
8-12.102. ScoQe The provisions of this chapter shall apply to all unreinforced
masonry buildings.
Exceptions:
A. This chapter shall not apply to detached one or two family dwellings and
detached apartment houses containing less than 5 dwelling units and used
solely for residential purposes.
B. This chapter shall not apply to warehouses and similar buildings used for
emergency services or supplies. (warehouses that have been converted to
retail, office, commercial, or residential occupancies are not exempt).
Ordinance No. 226
Exhibit "An
Page No. 3
C. This chapter shall not apply to buildings owned by the Federal or state
Government. (Buildings owned by local jurisdictions are not exempt).
All conforming and legal nonconforming buildings that are required to be
strengthened by alteration as a result of this chapter shall not be required to
comply with current site improvement standards of the City of Atascadero Zoning
Ordinance, including parking and landscaping.
In the event a building owner does not agree with zoning or signage conditions, he
or she may seek relief through appeal to the Planning Commission.
8-12.103. DEFINITIONS For purposes of this chapter, the applicable definitions in
Sections 2302 and 2312 of the uniform Building Code (1) shall apply:
Essential Building: Any building housing a hospital or other medical facility
having surgery or emergency treatment areas; fire or police stations; municipal
government disaster operation and communication centers.
High Risk Building: Any building not classified an essential building.
EZCEPTIONs
A high risk building shall not include the following:
A. Any building having exterior walls braced with masonry crosswalls or wood
frame crosswalls spaced less than 40 feet apart in each story.
Crosswalls shall be full story height with a minimum length of 14 times the
story height.
unreinforced Masonry Bearing wall: A masonry wall having all of the following
characteristics:
1. Provides the vertical support for a floor or roof.
2. The total superimposed load is over 200 pounds per linear foot.
3. The area of reinforcing steel is less than 50 percent of that required by 8-
12.107.
Ordinance No. 226
Exhibit 'A"
Page No. 4
8-12.104. RATING CLASSIFICATIONS The rating classifications shown in Table No. 12-
A are hereby established and each building within the scope of this chapter shall
be placed in one such rating classification by the Building Official.
SZCSPTION:
For the purpose of this chapter, portions of buildings constructed to act
independently when resisting seismic forces may be placed in separate rating
classifications.
8-12.105. GENERAL REMIREMSNTS The owner of each building within the scope of this
chapter shall cause a structural analysis of the building to be made by a civil or
structural engineer or architect licensed by the State of California. If the
building does not meet the minimum earthquake standards specified in this chapter,
the owner shall either cause it to be structurally altered to conform to such
standards; or cause the building to be demolished.
The owner of each building within the scope of this chapter shall comply with the
requirements set forth above by submitting to the Building Official for review
within the stated time limits:
1. on or before January 1, 1994, a structural analysis, which is subject to
approval by the Building Official, and which shall demonstrate that the
building meets the minimum requirements of this Chapter; or
2. On or before January 1, 1994, a structural analysis and plans for the proposed
structural alterations of the building necessary to comply with the minimum
requirements of this chapter; or
3. On or before January 1, 1994, plans for the demolition of the building.
After plans are submitted and approved by the Building Official, the owner shall
obtain a building permit, commence and complete the required construction within the
time limits set forth in Table No. 12-B.
8-12.106. ADMINISTRATION
1. Service of order. The Building Official shall issue an order, as provided in
8-12.106.(2), to the owner of each building within the scope of this chapter
within sixty (60) days from the effective date of these regulations.
2. Contents of order. The order shall be in writing and shall be served either
personally or by certified or registered mail upon the owner as shown on the
last equalized assessment, and upon the person, if any, in apparent charge or
control of the building. The order shall specify that the building has been
determined by the Building Official to be within the scope of this chapter
and, therefore, is required to meet the minimum, seismic standards of this
chapter. The order shall specify the rating classification of the building
and shall be accompanied by a copy of 8-12.105 which sets forth the owner s
alternatives and time limits for compliance.
Ordinance No. 226
Exhibit "A"
Page No. 5
3. AVVeal Form Order. The owner or person in charge of or in control of the
building may appeal to the Board of Appeals the Building Official's initial
determination that the building is within the scope of this chapter. Such appeal
shall be filed with the Board in accordance with TITLE 8 - BUILDING REGULATIONS
8-1.104.(e).
Appeals or request for slight modifications from any other determinations, order or
actions by the Building Official pursuant to this chapter, shall be made in accordance
with the normal appeal procedures established in this code.
4. Recordation. At the time that the aforementioned order is served, the Building
official shall file with the office of the County Recorder a certificate stating
that the subject building is within the scope of Chapter 12 - Earthquake Hazard
Reductions in Existing Unreinforced Nasonry Buildings. The certificate shall
also state that the owner thereof has been ordered to structurally analyze the
building and to structurally alter or demolish it where it is not found to comply
with Chapter 12.
If the building is found not to be within the scope of this chapter, or as a result of
structural alterations or an analysis is found to be structurally capable of resisting
minimum seismic forces required by this chapter; or is demolished; the Building
Official shall file with the Office of the County Recorder a certificate terminating
the status of the subject building as being classified within the scope of Chapter 12 -
Earthquake Hazard Reduction in Existing Unreinforced Nasonry Buildings.
5. Enforcement. if the owner or other person in charge or control of the subject
building fails to comply with any order issued by the Building official pursuant
to this chapter within any of the time limits set forth in 8-12.105, the Building
Official shall order the entire building vacated and remain vacated until such
order has been complied with. If compliance with such order has not been
accomplished within 90 days after the date the building has been ordered vacated,
or by such additional time as may have been ordered vacated, or by such
additional time as may have been granted by the Appeals Board, the Building
Official may order demolition of the building in accordance with the Abatement
of Dangerous Building provisions in this code.
8-12.107. ANALYSIS AND DESIGN
1. General. Every structure within the scope of this Division shall be analyzed and
constructed to resist minimum total lateral seismic forces assumed to act
nonconcurrently in the direction of each of the main axes of the structure in
accordance with the following equation:
V = ZCIW + We value of ZCI RW need not exceed the values set forth on Table 12-D.
SZCEPTION: The Building Official, upon receipt of adequate justification prepared by
a civil or structural engineer or architect licensed by the State of California, may
accept structural analysis and design in accordance with the latest edition of the
Uniform Code for Building Conservation, published by the International Conference of
Building officials, as an alternate method of compliance with the provisions of this
chapter.
Ordinance No. 226
Exhibit "A"
Page No. 6
2. Lateral Forces on Elements of Structures. Parts or portions of structures shall
be analyzed and designed for lateral loads in accordance with 8-12.107(a) of the
chapter and 2312(g) of the Uniform Building Code but not less than the value from
the following equation:
SaC8PTI0l�: Fp = ZICp wp (UBC 2312)
Unreinforced masonry walls in buildings that are not of a Class I rating may be
analyzed in accordance with Section 8-12.108.
The value of Cp need not exceed the values set forth in Table 12-F.
3. Anchorage and interconnection. Anchorage and interconnection of all parts,
portions and elements of the structure shall be analyzed and designed for lateral
forces in accordance with Table No. 12-F of this code and the equation Fp = ZECp
wp as modified by Table No. 12-E. Minimum anchorage of masonry walls to each
floor or roof shall resist a minimum force of 200 pounds per linear foot acting
normal to the wall at the level of the floor or roof.
4. Level of Required Repair. Alterations and repairs required to meet the
provisions of this chapter shall comply with all other applicable requirements
of the Uniform Building Code unless otherwise specifically provided for in this
chapter.
5. Required Analysis.
(a) general. Except as modified herein, the analysis and design relating to
the structural alteration of existing structures within the scope of this
chapter shall be in accordance with the analysis specified in Chapter 23
of the UBC.
(b) Continuous Stress Path. A complete, continuous stress path from every
part or portions of the structure to the ground shall be provided for the
required horizontal forces.
(c) Positive Connections. All parts, portions or elements of the structure
shall be interconnected by positive means.
6. Analysis Procedures.
(a) General. Stresses in materials and existing construction utilized to
transfer seismic forces from the ground to parts or portions of the
structure shall conform to those permitted by the Uniform Building Code
and those materials and types of construction specified in 8-12.108.
(b) Connections. Materials and connectors used for interconnection of parts
and portions of the structures shall conform to the Uniform Building Code.
Nails may be used as part of an approved connector.
Ordinance No. 226
Exhibit A"
Page No. 7
(c) Unreinforced Masonry walls. Except as modified herein, unreinforced
masonry walls shall be analyzed as specified in UBC Sections 2406, 2407
and 2408 to withstand all vertical loads as specified in Chapter 23 of the
Uniform Building Code in addition to the seismic forces required by this
chapter. The 50 percent increase in the seismic force factor for shear
walls as specified in Section 2407 (h) 4F of the Uniform Building Code may
be omitted in the computation of seismic loads to existing shear walls.
No allowable tension stress will be permitted in unreinforced masonry
walls. walls not capable of resisting the required design forces specified in this
chapter shall be strengthened or shall be removed and replaced.
SECSPTION:
A. Unreinforced masonry walls in buildings not rated as a Class I building pursuant
to Table No. 12-A may be analyzed in accordance with 8-12.108.
B. An unreinforced masonry wall which carries no design loads other than its own
weight may be considered as veneer if it is adequately anchored to new supporting
elements.
7. Combination of vertical and Seismic forces.
(a) New Materials. All new materials introduced into the structure to meet
the requirements of this section which are subjected to combined vertical
and horizontal forces shall comply with Section 2303 of the Uniform
Building Code.
(b) Existing Materials. when stresses in existing lateral force resisting
elements are due to a combination of dead loads plus live loads plus
seismic loads, the allowable working stress specified in the Uniform
Building Code may be increased 100 percent. However, no increase will be
permitted in the stresses allowed in Section 8-12.108, and the stresses in
members due only to seismic and dead loads shall not exceed the values
permitted by Section 2303 (d) of the Uniform Building Code.
(c) Allowable Reduction of Bending Stress by Vertical Load. in calculating
tensile fiber stress due to seismic forces required by this chapter, the
maximum tensile fiber stress may be reduced by the full direct stress due
to vertical dead loads.
8-12.108. NRTERxALs OF CONSTRUC'T'ION
1. General. All materials permitted by the Uniform Building Code including their
appropriate allowable stresses and those existing configurations of materials
specified herein may be utilized to meet the requirements of this chapter.
Ordinance No. 226
Exhibit "All
Page No. 8
2, Existing Materials.
(a) Unreinforced Masonry walls. Unreinforced masonry walls analyzed in
accordance with this Section may provide vertical support for roof and
floor construction and resistance to lateral loads. The facing and
backing of such walls shall be bonded so that not less than 4 percent of
the exposed face area is composed of solid headers extending not less than
4 inches into the backing. The distance between adjacent full-length
headers shall not exceed 24 inches vertically or horizontally. where the
backing consists of two or more wythes, the header shall extend not less
than 4 inches into the most distant Wythe, or the backing wythes shall be
bonded together with separate headers whose area and spacing conform to
the foregoing.
Tension stresses due to seismic forces normal to the wall may be neglected
if the walls do not exceed the height to thickness ratio in Table No. 12-G
and the in-plane shear stresses due to seismic loads as set forth in Table
No. 12-J.
if the wall height-thickness ratio exceeds the specified limits, the wall
may be supported by vertical bracing members designed in accordance with
8-12.108. The deflections of such bracing member at design loads shall
not exceed one-tenth of the wall thickness.
EZCEPTIONs
The wall may be supported by flexible vertical bracing members designed in accordance
with 8-12.107, if the deflection at design loads is not less than one-quarter nor more
than one-third of the wall thickness.
All vertical bracing members shall be attached to floor and roof construction for their
design loads independently of required wall anchors. Horizontal spacing of vertical
bracing members shall not exceed one-half the unsupported height of the wall nor ten
feet.
The wall height may be measured vertically to bracing elements other than a floor or
roof. Spacing of the bracing elements and wall anchors shall not exceed six feet.
Bracing elements shall be detailed to minimize the horizontal displacement of the wall
by components of vertical displacements of the floor or roof.
(b) Existing Roof Floors walls Footings and wood Framing. Existing
materials including wood shear walls utilized in the described
configuration may be used as part of the later load resisting system,
provided that the stresses in these materials does not exceed the value
shown in Appendix Table No. 12-H.
3. Strengthening of Existing Materials. New materials including wood shear walls
may be utilized to strengthen portions of the existing seismic resisting systems
in the described configurations provided that the stresses do not exceed the
values shown in Table No. 12-I.
Ordinance No. 226
Exhibit "A"
Page No. 9
4. Alternate Materials. Alternate materials, designs and methods of construction
may be approved by the Building official in accordance with the provisions of the
Uniform Building Code.
5. Minimum Acceptable Quality of Existina Unreinforced Masonry walls:
(a) General Provisions. All unreinforced masonry walls utilized to carry
vertical loads and seismic forces parallel and perpendicular to the wall
plane shall be tested as specified in this subsection. All masonry
quality shall equal or exceed the minimum standards established herein or
shall be removed and replaced by new materials. Alternate methods of
testing may be approved by the Building Official. The quality of mortar
in all masonry walls shall be determined by performing in-place shear
tests or by testing eight inch diameter cores. Alternative methods of
testing may be approved by the Building Official. Nothing shall prevent
pointing with mortar of all the masonry wall joints before the tests are
first made. Prior to any pointing, the mortar joints must be raked and
cleaned to remove loose and deteriorated mortar. Mortar for pointing
shall be Type S or N except that masonry cements shall not be used. All
preparation and mortar pointing shall be done under the continuous
inspection of a special inspector certified to inspect masonry or
concrete, and approved by the Building Official. At the conclusions of
the inspections of, the inspector shall submit a written report to the
licensed engineer or architect responsible for the seismic analysis of the
building setting forth the result of the work inspected. Such report
shall be submitted to the Building Official for approval as part of the
structural analysis. All testing shall be performed in accordance with
the requirements specified in this subsection by a testing agency approved
by the Building Official. An accurate record shall be kept of all such
tests and of their locations in the building, and these results shall be
submitted to the Building Official for approval as part of the structural
analysis.
(b) Number and Location of Tests. The minimum number of tests shall be two
per wall or line of wall elements resisting a common force, or 1 per 1500
square feet of wall surface, with a minimum of eight tests in any case.
The exact test or core location shall be determined at the building site
by the licensed engineer or architect responsible for the seismic analysis
of the subject building.
(c) In-Place Shear Tests. The bed joints of the outer Wythe of the masonry
shall be tested in shear by laterally displacing a single brick relative
to the adjacent bricks in that Wythe. The opposite head joint of the
brick to be tested shall be removed and cleaned prior to testing. The
minimum quality mortar in 80 percent of the shear tests shall not be less
than the total of 30 psi plus the axial stress in the wall at the point of
the test. The shear stress shall be based on the gross area of both bed
joints and shall be that at which movement of the brick is first observed.
Ordinance No. 226
Exhibit "A"
Page No. 10
(d) Core Tests. A minimum number of mortar test specimens equal to the number
of required cores shall be prepared from the cores and tested as specified
herein. The mortar joint of the outer Wythe of the masonry core shall be
tested in shear by placing the circular core section in a compression
testing machine with the mortar bed joint rotated 15 degrees from the axis
of the applied load. The mortar joint tested in shear shall have an
average ultimate stress of 20 psi based on the gross area. The average
shall be obtained from the total number of cores made. If test specimens
cannot be made from cores taken, then the shear value shall be reported as
zero.
6. Testing of Shear Bolts. One-fourth of all new shear bolts and dowels embedded
in unreinforced masonry walls shall be tested by a Special Inspector using a
torque calibrated wrench to the following minimum torques:
1/2" diameter bolts or dowels = 40 foot-lbs.
5/8" diameter bolts or dowels = 50 foot-lbs.
3/4" diameter bolts or dowels = 60 foot-lbs.
No bolts exceeding 3/4" shall be used. All nuts shall be installed over
malleable iron or plate washers when bearing on wood and heavy cut washers when
bearing on steel.
7. Determination of Allowable stresses for Design Methods based on Test Results.
(a) Design Shear Values. Design seismic in-plane shear stresses shall be
substantiated by tests performed as specified in 8-12.108(5.c & d).
Design stresses shall be related to test results obtained in accordance
with Table No. 12-J. Intermediate values between 3 and 10 psi may be
interpolated.
(b) Design Compressions and Tension Values. Compression stresses for
reinforced masonry having a minimum design shear value of 3 psi shall not
exceed 100 psi. Design tension values for unreinforced masonry shall not
be permitted.
Ordinance No. 226
Exhibit "A"
Page No. 11
8. Tests Required. Five percent of the existing rod anchors utilized as all or part
of the required wall anchors shall be tested in pullout by an approved testing
laboratory. The minimum number tested shall be four per floor, with two tests
at walls with joist framing into the wall and two tests at walls with joists
framing into the wall and two tests at walls with joists parallel to the wall.
The test apparatus shall be supported on the masonry wall at a minimum distance
of the wall thickness from the anchor tested. The rod anchor shall be given a
pre-load of 300 lbs. prior to establishing a datum for recording elongations.
The tension test load reported shall be recorded at one-eighth inch relative
movement of the anchor and the adjacent masonry surface.
Results of all tests shall be reported. The report shall include the test
results as related to the wall thickness and joist orientation. The allowable
resistance value of the existing anchors shall be 40 percent of the average of
those tested anchors having the same wall thickness and joist orientation.
9. Test Procedures. Qualification tests for devices used for wall anchorage shall
be tested with the entire tension load carried on the enlarged head at the
exterior face of the wall. Bond on the part of the device between the enlarged
head and the interior wall face shall be eliminated for the qualification tests.
The resistance value assigned the device shall be 20 percent of the average of
the ultimate loads.
8-12.109. INFORMA!CIom RBOUIRBD ON PLANS.
1. General. In addition to the seismic analysis required elsewhere in this chapter,
the licensed engineer or architect responsible for the seismic analysis of the
building shall determine and record the information required by this Section on
the approved plans.
2. construction Details. The following requirements with appropriate construction
details shall be made part of the approved plans:
(a) All unreinforced masonry walls shall be anchored at the roof level by
tension bolts through the wall as specified in Table 12-1, or by approved
equivalent at a maximum anchor spacing of six feet.
All unreinforced masonry walls shall be anchored at all floors with tension bolts
through the wall or by existing rod anchors at the maximum anchor spacing of six feet.
All existing rod anchors shall be secured to the joists to develop the required forces.
The Building Official may require testing to verify the adequacy of the embedded ends
of existing rod anchors.
Tests when required shall conform to 8-12.108(8.)
when access to the exterior face of the masonry wall is prevented by proximity
of an existing building, wall anchors conforming to items 5 and 6 in Table 12-1
may be used.
Alternative devices to be used in lieu of tension bolts for masonry gall
anchorage shall be tested as specified in 8-12.108(9.).
Ordinance No. 226
Exhibit 'A"
Page No. 12
(b) Diaphragm chord stresses of horizontal diaphragms shall be developed in
existing materials or by addition of new materials.
(c) where trusses and beams other than rafters or joists are supported on
masonry, ledgers or columns shall be installed to support vertical load of
the roof or floor members.
(d) Parapets and exterior wall appendages not capable of resisting the forces
specified in this Chapter shall be removed, stabilized or braced to insure
that the parapets and appendages remain in their original position.
(e) All deteriorated mortar joints in unreinforced masonry walls shall be
pointed with type S or N mortar (masonry cements shall not be used).
Prior to any pointing, the wall surface must be raked and cleaned to
remove loose and deteriorated mortar. All preparation and pointing shall
be done under the continuous inspection of a special inspector certified
to inspect masonry or concrete, and approved by the Building Official. At
the conclusion of the project, the inspector shall submit a written report
to the Building Official setting forth the portion of work inspected.
(f) Repair details shall be prepared for any cracked or damaged unreinforced
masonry wall required to resist forces specified in this Chapter.
3. Existing Construction. The following existing construction information shall be
made part of the approved plans:
(a) The type and dimensions of existing walls and the size and spacing of
floor and roof members.
(b) The extent and type of existing wall anchorage to floors and roof.
(c) The extent and type of parapet corrections, if any, which were performed
in accordance with the uniform Building Code.
(d) Accurately dimensioned floor plans and masonry wall elevations showing
dimensioned openings, piers, wall thickness and heights.
(e) The location of cracks or damaged portions of unreinforced masonry walls
requiring repairs.
(f) The type of interior wall surfaces and whether reinstalling or anchoring
of ceiling plaster is necessary.
(g) The general condition of the mortar joints and whether the joints need
pointing.
Ordinance No. 226
Exhibit ^A"
Page No. 13
TABLE NO. 12—A
RATING CLASSIFICATIOMS
TYPE OF BUILDING CLASS
Essential Building I
High Risk Building II
APPENDIX TABLE NO. 12—B
TIME LIMITS FOR COMPLIANCE
Bldg. Permit Fran Date Of
submittal Dead- Issuance Deadline
Rating Occupant line for Rehab. for strengthening Camence Complete
Classifica- Load Plans or Demolition within within
tion
I Any January 1, 1994 January 1, 1996 180 Days 2 years
Ii Any January 1, 1994 January 1, 1996 180 Days 2 years
APPENDIX TABLE NO. 12-C
(NOT USED]
Ordinance No. 226
Exhibit "A
Page No. 14
TABLE 12-D
HORIZONTAL FORCE FAC'T'ORS BASED
ON RATING CLASSIFICATION
RATING
CLASSIFICATION ZCI RN
I 0.229
II 0.183
TABLE NO. 12-E
HORIZONTAL FORCE FACTORS ^ZI"
FOR PARTS OR PORTIONS OF STRUCTURES
RATING
CLASSIFICATION 81
I 0.50
II 0.40
Ordinance No. 226
Exhibit "A"
Page No. 15
TABLE 12-F
HORISOWZAL FORCE FACTOR Cp
Applicable to Rigid Items
S[.SEEE'J!S OF STRUCTURES AND HERNMTKKIVILMRAL
VALUE OF Cp
C06@ONEMS
See Section 8.12.106(2) for use of Cp.
See Im Tahip Up 93-P (19W for fnatnotp referan_es
I. Part of Portion of Structure
1. Walls, including the following:
a. Unbraced (cantilevered) parapets.. . . . . . .. . .. . . . . . . . . . . . . . .. . 2.00
b. Other exterior wails above the ground floor.. .. .. .. . . . . .. . . 0.75
c. All interior bearing and nonbearing walls and partitions.. . . . . .. . . 0.75
d. Masonry or concrete fences over 6 feet high. .. . . . . . . . . .. . . . . . . . . . 0.75
2. Penthouse (except where framed by an extension of the
building frame). . . . . . . . .. . . . . •
. . . . . . . . . . . . 0.75
3. Connections for prefabricated structuralelements other than walls,
with force applied at center of gravity. ... . . . . .. . . ... .. . . .. .. . . . . . 0.75
4. Diaphragms. .. .. . . . . ... . . . .. . . .. .. . . .. . .. .. . . ... . .. . . . . . . . . . . . . . . . . . . .. --
II. Nonstructural Components
1. Exterior and interior ornamentations and appendages... .. . . . . . . .. . . . . . . 2.00
2. Chimneys, stacks, trussed towers, and tanks on legs.
a. supported on or projecting as an unbraced cantilever above
the roof more than one-half its total height. . . . .. . . . . .. 2.00
b. All others, including those supported below the roof with
unbraced projection above the roof less than one-half its
height, or braced or guyed to the structural frame at or
above its center of mass.. . . . . .. . . . . . . . . . . ... . . .. . .. .. . . . . .. . .. . . 0.75
3. Signs and billboards.. . . .. . . . . . ... . 2.00
4. Mechanical, plumbing and electrical equipment and machinery and
associated piping. . .. .... . . . . . . . . . .. 0.75
5. Tanks and vessels (plus contents), including support systems
and anchorage. . . ... . .... . . . ... ... . . .. . . . . . . . .. .. . ... . ... . . . . .. . . . 0.75
6. Storage racks (include contents).. . .. ... . . . .. . . . . . .... . . . .. . . . . .. . . 0.75
7. Anchorage for permanent floor-supported cabinets and bookstacks
more than 5 feet in height (includes contents).. .. ...... . . . 0.75
S. Anchorage for suspended ceilings and light fixtures - see also
Section 4701(e). . .. . . . .. . . ... . .. . . .. . ... . . .. . . . . . . .. . . . . . . . . . . . .. . .. . . 0.75
9. Access floor systems. .. .. . . . .. . .. . . . . . . . ... . .. . .. ... . . . . . . . . . . .... . . 0.75
Ordinance No. 226
Exhibit "All
Page No. 16
TABLE NO. 12-G
ALLONABLE VALUE OF NEXOMT-THUMESS RATIO
OF UNREINFORCED MASONRY NALLS WITH KXNINUN
QUALITY MORTAR (1) (2)
VMLL LOCATION BUILDINGS WITH CROSSIMI" ALL OTHER
AS DEFINED BY SECTION AC2403 BUILDINGS
'falls of One Story Buildings 16 13
First story Mall of Multi-Story 16 15
Buildings
stalls in TOP Story Of Multi-story 14 g
Buildings
All Other Malls 16 13
(1) Minim quality Mortar shall be determined by laboratory testing in accordance
with section 8.12.108(5).
(2) Appendix Table 12-9 is not applicable to buildings of rating
Classification I. halls of buildings within rating Classification I shall
be analysed in accordance with Section 8.12.107(6).
Ordinance NO. 226
Exhibit "A"
Page NO. 17
TABLE NO. 12—H
VALVES FOR EXISTING NATEUTAW
EXISTING NaTSRIAW OR
CONFIGURATION OF JULTERIALS *(I) ALLAMBL.E VALUES
1. HORIZONTAL DIAPHRA®tS
a. Roofs with straight sheathing and roofing 100 lbs. per foot for seismic
applied directly to the sheathing. shear.
b. Roofs with diagonal sheathing and roofing 400 lbs. per foot for seismic
applied directly to the sheathing. shear.
C. Floors with straight tongue and groove 150 lbs. per foot.
sheathing.
d. Floors with straight sheathing and finished 300 lbs. per foot for seismic
wood flooring. shear.
e. Floors with diagonal sheathing and finished 450 lbs. per foot for seismic
wood flooring. shear.
f. Floors or roofs with straight sheathing and Add 50 lbs. per foot to the
plaster applied to the joist or rafters. *(2) allowable values for Items Is
and lc.
2. SHEAR aALLS
Wood stud walls with lath and plaster. 100 lbs. per foot each side
for seismic shear.
3. PLAIN CONCRETE FOOTINGS. f = 1500 psi unless otherwise
shown by tests.
4. DOUGLAS FIR WOOD. Allowable stress same as no. 1
D.F. *(3)
5. REINFORCING STEEL. f = 18,000 lbs. per square
inch maximum. *(3)
6. STRUCTURAL STEEL. f = 20,000 lbs. per square
inch maximum. *(3)
(1) Material must be sound and in good conditions.
(2) The roof lath and plaster must be re-attached to existing joists or rafters in a
manner approved by the Building Official.
(3) Stresses given may be increased for combinations of loads as specified in
Section 8.12.107(7)(b).
Ordinance No. 226
Exhibit A'
Page No. 18
TABLE 110. 12-I
ALLOWABLE VALUES OF NEN MATERIALS USED IN
COWUNCTION WITH EXISTING CONSTRUCTION (1)
EXISTING MATERLALS OR ALLOIWBLE VALUES
CONFIGURATION OF MATR XALS (1) FROM UBC TABLES
1. HORIZONTAL DIAPHRAGMS
Plywood sheathing applied directly over existing Same as specified in Tables No. 25-1
straight sheathing with ends of plywood sheets of the USC for blocked diaphragms.
bearing on joists or rafters and edges of
plywood located on center of individual
sheathing boards.
2. SHEAR MALLS
a. Plywood sheathing applied directly over Same as values specified in Tables
existing wood studs. No value shall be 25-K of the UBC.
given to plywood applied over existing
plaster or wood sheathing.
b. Drywall or plaster applied directly over 75% of the values specified in Table
existing wood studs. No. 47-1 of the UBC.
3. SHEAR BOLTS
Shear bolts and shear dowels embedded a minimum 100% of the values for solid masonry
of 8 inches into unreinforced masonry walls. specified in Table no. 24E of UBC.
Bolt centered in a 2h inch diameter hole with No values larger than those given
dry-pack or non-shrink grout around for k inch bolts shall be used.
circumference of bolt or dowel *(1)
4. TENSION BOLTS
Tension bolts and tension dowels extending 1200 lbs. per bolt or dowel.
entirely through unreinforced masonry walls
secured with bearing plates on far side of wall
with at least 30 sq. inches of area. *(2)
5. MALL ANCHORS (8-12.109(2)(a))
a. Bolts extending to the exterior face of 600 lbs. per bolt.
the wall with a 24 inch round plate under
the head. Installed as specified for
shear bolts. Spaced not closer than 12
inches on centers. *(1)(2)
b. Bolts or dowels extending to the exterior 1200 lbs. per bolt or dowel.
face of the wall with a 2; inch round
plate under the head and drilled at as
angle of 22h degrees to the horizontal.
installed as specified in shear bolts.
*(l)(2)
Ordinance No. 226
Exhibit "A"
Page No. 19
TABLE 12—I — COST'D
6. INFII.LED WALLS
Reinforced masonry infilled openings in existing Same as values specified
unreinforced masonry walls with keys or dowels to for unreinforced masonry walls.
match reinforcing.
7. RHXNFORCBD MASONRF
Masonry piers and walls reinforced per Section 2407 Same values as specified in
of the UBC. Chapter 24, UBC.
8. REINFORCED CONCRETE
Concrete footings, walls, and piers reinforced as Same values as specified in
specified in Chapter 26 of the UBC and designed for Chapter 26, UBC.
tributary loads.
9. EXISTING FOUIIDATION LOADS
Foundation loads for structures exhibiting no Calculated existing foundation
evidence of settlement. loads due to maximum dead load
plus live load may be increased
25% for dead load and may be
increased 50% dead load plus
seismic load required by this
Division.
NOTES:
(1) Holts and dowels to be tested as specified in Section 8.12.107(6)
(2) Bolts and dowels to be 1/2 inch minimum in diameter.
Ordinance No. 226
Exhibit "A"
Page No. 20
TABLE 12-J
AtZArIABLE SHEAR STRESS FOR TESTED
UNREINFORCED MASONRY MALL
Eighty Percent of Average Test Results of Cores in Seismic in-plane Shear
Test Results In PSI PSI based on Gross Area (1)
Not Less Than
30 plus axial stress 20 3 psi
40 plus axial stress 27 4 psi
50 plus axial stress 33 5 psi
100 plus axial stress 67 or more 10 psi max
or more
(1) Allowable shear stress may be increased by addition of 10% of the axial stress
due to the weight of the wall directly above.
Ordinance No. 226
Exhibit "A"
Page No. 21
GXJDSSARY OF SIMlOLS AND NOTATIONS
C = Numerical coefficient as specified in UBC Section 2312 (e) 2B.
CP Numerical coefficient as specified in UBC Section 2312 (g) and
given in Table No. 23-P.
f.0 = Specified compressive strength of concrete, psi.
Fp = Lateral forces on a part of the structure.
fT = That portion of the base shear, V, considered concentrated at the
top of the structure in addition to Fn.
hN - Height in feet above the base to Level i, n, or x respectively.
I = Importance Factor given in UBC Table No. 23-L.
% = Numerical coefficient given in Tables 23-0 and 23-Q of UBC.
V = The total design lateral force or shear at the base.
M _ The total seismic dead load as defined in UBC Section 2312(e)1.
NP = The weight of an element or component.
8 = Numerical coefficient of 0.40 for Seismic Zone 4.